| Room Code | WLB-I |
| Net Room Area Briefed | 10 |
| Hours of Operation | Available 24 Hours |
| Occupancy | 1 staff |
| Description / Special Requirements | An area defined by mobile screens in which metal fabrication procedures can be undertaken. Storage will be required for proptective clothing, equipment and materials. The Welding Booth will be located with direct access to the Fitters/Plumbers Worksop area with close access to a Cleaning Bay. |
| Amendment | 24.10.2010 First Draft 21.04.2011 Room Fabric and FF modified 03.09.2023 RDS updated |
| ID | Fabric | Material | Finish | Specification | Selection | Remarks |
| 5140 | Ceiling | Concrete | Paint | Acrylic | ||
| 1280 | Floor finish | Concrete | Trowel | Sealed | ||
| 3000 | Wall finish | Paint | Acrylic, washable | |||
| 3110 | Wall finish | Stainless steel | Linished | Splashback | integral with sink bench |
| ID | Description | Category | Group | Qty | Selection / Remarks |
| 1121 | Bench: work | Furniture/ Fitting | 3 | 1 | metal, free standing |
| 13640 | Cupboard: metal, 2 door | Furniture/ Fitting | 3 | 1 | |
| 19155 | Screen: welding, mobile | Furniture/ Fitting | 3 | 4 | |
| 20150 | Bench: sink, stainless steel | Metalwork | 1 | 1 | with integrated sink & splashback |
| 24040 | Vice | Furniture/ Fitting | 3 | 1 |
| ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
| 1623 | Welder: Oxy-acetylene | 3 | 1 | |||||||||
| 40407 | Tapware: laundry | 1 | 1 | ___ | ___ | yes | yes | yes | ___ | ___ | ___ | |
| 49400 | Sink: laundry, single | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | cooling-off sink |
| ID | Description | Service Category | Qty | Selection / Remarks |
| 5015 | Ventilation | HVAC | ||
| 5019 | Exhaust | HVAC | variable speed | |
| 2189 | General LED | Lighting | ||
| 2577 | PO: Double | Power | 1 | to wall |
| 2587 | PO: Special: for equipment | Power | 1 | 3 phase |
| 2587 | PO: Special: for equipment | Power | 2 | 15 amp |