Edit it in Health Facility Briefing System (HFBS) | |||
---|---|---|---|
![]() |
Edit this room data or print a PDF using the HFBS - Health Facility Briefing System. Customise this room data for your project, or add it to an existing health facility brief in HFBS Briefing Module. | Open HFBS |
Room Layout Sheet | |||
---|---|---|---|
![]() |
Download a PDF Room Layout Sheet (RLS) for this standard component. | Free | View |
Other Files | |||
---|---|---|---|
![]() |
Buy an edible AutoCAD DWG Room Layout Sheet (RLS) for this standard component. | $2.99 |
Room Code | GYAH-60-I |
Net Room Area Briefed | 60 |
Hours of Operation | 8am to 6pm daily |
Occupancy | Up to 6 patients/ hour; up to 4 staff |
Description / Special Requirements | The Gymnasium provides for patient evaluation, rehabilitation exercise activities, therapy and ambulation training. An external outlook is desirable. The Gym area will require access for wheelchairs and staff handwashing facilties. The equipment to be used in this area will be dependent on the funtion of the gym and the Operational Policy. Acoustics: Acoustic privacy required. Body protected electrical area Special Design Requirements - Floors, walls and ceilings must be structurally able to support exercise and weight training equipment that may be required in the gym |
Amendment | 24.10.2010 First Draft 02.05.2011 Fabric, FF & Services updated 02.03.2017 Description, Fabric updated |
ID | Fabric | Material | Finish | Specification | Selection | Remarks |
1000 | Floor finish | Vinyl | Standard slip resistant | Seamless, coved | ||
2000 | Skirting | Vinyl | Prefinished | Floor vinyl coved, 150mmH | cushioned vinyl optional | |
3000 | Wall finish | Paint | Acrylic, washable | |||
7001 | Windows | desirable | ||||
8040 | Door protection | Composite | Prefinished PVC | To door frame | ||
3022 | Wall finish | Resinate, 6mm | Prefinished | Splashback | to basin & sink, tiles or other smooth impervious finish also acceptable | |
6025 | Cornice | Aluminium | Powdercoat | shadow line | ||
8010 | Door protection | Composite | Prefinished PVC | Protection plate to 900 AFFL | ||
5060 | Ceiling | Acoustic | Prefinished | Drop-in tiles, 600x1200 mm | flush set plasterboard acoustic ceiling also acceptable | |
9125 | Doors | Solid Core/ Glass | Paint | 1 1/2 leaf, observation panel | Patient Entry/Exit; 1400 mm clear opening, lockable |
ID | Description | Category | Group | Qty | Selection / Remarks |
1050 | Bench: laminate | Furniture/ Fitting | 1 | 1 | optional |
1250 | Blind: Venetian | Metalwork | 3 | 1 | 1 to each external/ internal window, if provided |
1650 | Chair: client | Furniture/ Fitting | 3 | 4 | |
3350 | Clock: battery operated | Furniture/ Fitting | 3 | 1 | |
4410 | Cupboard: under bench | Furniture/ Fitting | 1 | 1 | optional |
4430 | Cupboard: drawer unit | Furniture/ Fitting | 1 | 1 | under bench, optional |
4460 | Cupboard: wall mounted | Furniture/ Fitting | 1 | 1 | over bench; adjustable shelves; optional |
4600 | Curtain track: bed screen | Metalwork | 1 | 2 | to plinth spaces |
5000 | Curtain: bed screen | Furniture/ Fitting | 3 | 2 | to plinth spaces |
6154 | Dispenser: paper/ hand towel | Furniture/ Fitting | 2 | 2 | to basin & sink |
6156 | Dispenser: soap | Furniture/ Fitting | 2 | 2 | to basin & sink |
7520 | Exercise bicycle | Furniture/ Fitting | 3 | 2 | optional |
7530 | Exercise stairs | Furniture/ Fitting | 3 | 1 | optional |
8866 | Plinth: single | Furniture/ Fitting | 3 | 1 | |
8867 | Plinth: double | Furniture/ Fitting | 3 | 1 | |
13645 | Steel mesh: framed, ceiling mount | Metalwork | 1 | 2 | to plinths, optional |
13646 | Steel mesh: framed, wall mount | Metalwork | 1 | 2 | to plinths, optional |
13800 | Mirror: full length | Metalwork | 1 | 1 | to one wall |
16780 | Parallel bars | Furniture/ Fitting | 3 | 1 | 1 set; removable |
18170 | Pulley weights: wall mounted | Furniture/ Fitting | 3 | 1 | optional |
24100 | Waste bin: paper, 20 Litre | Furniture/ Fitting | 3 | 1 | to basin |
ID | Description | Grp | Qty | Ele | Data | CdW | HtW | WmW | Tap | Dns | Gas | Selection / Remarks |
2800 | Basin: handwash, Type B | 1 | 1 | ___ | ___ | yes | ___ | yes | yes | yes | ___ | taps: sensor outlet; elbow action lever taps also acceptable |
47890 | Sink & drainer: single, 930mmL | 1 | 1 | ___ | ___ | yes | opt | opt | yes | yes | ___ | sink optional, provide hot water |
54510 | Telephone: handset, standard | 3 | 1 | ___ | yes | ___ | ___ | ___ | ___ | ___ | ___ | wall phone |
ID | Description | Service Category | Qty | Selection / Remarks |
1000 | Telephone: PABX | Communications | 1 | to wall phone |
1006 | Voice / Data outlet: double | Communications | 3 | 1 to each plinth space; 1 to bench |
5000 | Airconditioning | HVAC | ||
6000 | General fluorescent | Lighting | ||
8000 | Patient/ Staff call | Nurse Call | 2 | 1 to each plinth space; + indicator button & light |
8005 | Patient call handset | Nurse Call | 2 | 1 to each plinth space; call button on the handset |
8010 | Staff/ Nurse assist call | Nurse Call | 1 | + indicator button & light |
8080 | Emergency call | Nurse Call | 1 | + indicator button & light |
9001 | GPO: Double | Power | 10 | quantity will be determined by equipment to be used and Operational Policy |
9015 | GPO: Cleaner | Power | 1 | |
9040 | Body protected | Power |